dc.description.abstract | Evaporative cooling systems are a widely used technique in Mediterranean greenhouses. In this study, the
cellulose evaporative cooling pads most commonly used in this region were tested in the laboratory using a new methodology
in a wind tunnel to determine the water flow on the pad and air flow through it, as well as the water consumption and pressure
drop caused by each pad as a function of air speed. Greater water flow increased the pressure drop, but the main effect on
performance was caused by modifying the air flow through the pad. We recommend a range of air speeds through the pad
of 1 to 1.5 m s‐1, at which the pressure drop was between 3.9 and 11.25 Pa, depending on the type of pad and the water flow
applied. On the other hand, saturation efficiency ranged between 64% and 70%, while the amount of evaporated water varied
between 1.8 and 2.62 kg h‐1 K‐1 per square meter of pad area. | es |
dc.format | application/pdf | es |
dc.language.iso | eng | es |
dc.publisher | American Society of Agricultural and Biological Engineers | es |
dc.relation.ispartof | Transactions of the ASAE, 2010 (53) (2010 (2)), 565 p.-576 p.. | |
dc.rights | Attribution-NonCommercial-NoDerivatives 4.0 Internacional | * |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | * |
dc.subject | Evaporated water | es |
dc.subject | Evaporative cooling | es |
dc.subject | Fan and pad | es |
dc.subject | Greenhouse | es |
dc.subject | Heat and mass transfer | es |
dc.subject | Pressure drop | es |
dc.subject | Saturation efficiency | es |
dc.title | Influence of Water and Air Flow on the Performance of Cellulose Evaporative Cooling Pads Used in Mediterranean Greenhouses | es |
dc.type | info:eu-repo/semantics/article | es |
dcterms.identifier | https://ror.org/03yxnpp24 | |
dc.type.version | info:eu-repo/semantics/publishedVersion | es |
dc.rights.accessRights | info:eu-repo/semantics/openAccess | es |
dc.contributor.affiliation | Universidad de Sevilla. Departamento de Ingeniería Aeroespacial y Mecánica de Fluidos | es |
dc.relation.publisherversion | https://elibrary.asabe.org/abstract.asp?aid=29571 | es |
dc.identifier.doi | 10.13031/2013.29571 | es |
dc.contributor.group | Universidad de Sevilla. AGR268: Naturación Urbana e Ingeniería de Biosistemas | es |
idus.format.extent | 12 p. | es |
dc.journaltitle | Transactions of the ASAE | es |
dc.publication.volumen | 2010 (53) | es |
dc.publication.issue | 2010 (2) | es |
dc.publication.initialPage | 565 p. | es |
dc.publication.endPage | 576 p. | es |
dc.identifier.sisius | 8127 | es |